DPT01EX
  • Same day Shipment
    for stock items
  • 100% Customer
    Satisfaction
  • 365 Days
    Support on Call
  • Payment
    Secure System
  • Only Best
    Brands

DPT01EX

Available: In Stock
Rs. 12,500.00
Image

Futuristic Flameproof Differential Pressure Transmitter Series DPT01EX is specifically designed to measure positive, negative, or differential pressure within the ranges of ±25 Pa to ±20"WC. With its optional LED display, it offers convenient and intuitive pressure readings.

The DPT01EX Flameproof transmitter operates reliably in hazardous environments, and is suitable for use in Zone 1 and 2 areas. It is designed to meet the requirements of Gas Group IIA, IIB and IIC, T6.

In HVAC applications, the DPT01EX Flameproof transmitter is used for monitoring duct static pressure and filter differential pressure.

Specifications:

  • DP Sensing Technology  : Piezo resistive silicon sensor
  • Service                            : Air or non-corrosive gases
  • Measurement Range      : ±25 Pa to ±20”WC (Please refer ordering code)
  • Over Pressure                 : 3.6 PSI
  • Burst Pressure                 : 6 PSI
  • Accuracy                         : ±1% FS
  • Stability                           : ±1% FS per Year
  • Output Resolution          : 0.025%
  • Start up Time                  : 5 mSec
  • Response time                : 1 mSec
  • Output                            : 4-20mA / 0 to 10VDC
  • Display                            : 5 Digit LED Display (Optional)
  • Supply Voltage               : 24VDC / 24VAC ±10%
  • Operating Temperature  : -20° to +50°C

       Enclosure :

  • Material                                  : Di Cast Aluminum Alloy LM6
  • Type of Explosion Protection : EEx-d, IEC60079-1:2007
  • Zone Classification                 : Suitable for Zone 1 & 2
  • Gas Group                              : Suitable for Gas group IIA, IIB & IIC, T6
  • Ingress Protection                  : IP66, IEC60529-1:2001
  • Paint                                       : Epoxy Polyester powder coated
  • Cable Entry                             : ½” NPT double compression gland

    Futuristic Flameproof Differential Pressure Transmitter Series DPT01EX is specifically designed to measure positive, negative, or differential pressure within the ranges of ±25 Pa to ±20"WC. With its optional LED display, it offers convenient and intuitive pressure readings.

    The DPT01EX Flameproof transmitter operates reliably in hazardous environments, and is suitable for use in Zone 1 and 2 areas. It is designed to meet the requirements of Gas Group IIA, IIB and IIC, T6.

    In HVAC applications, the DPT01EX Flameproof transmitter is used for monitoring duct static pressure and filter differential pressure.

    Specifications:

    • DP Sensing Technology  : Piezo resistive silicon sensor
    • Service                            : Air or non-corrosive gases
    • Measurement Range      : ±25 Pa to ±20”WC (Please refer ordering code)
    • Over Pressure                 : 3.6 PSI
    • Burst Pressure                 : 6 PSI
    • Accuracy                         : ±1% FS
    • Stability                           : ±1% FS per Year
    • Output Resolution          : 0.025%
    • Start up Time                  : 5 mSec
    • Response time                : 1 mSec
    • Output                            : 4-20mA / 0 to 10VDC
    • Display                            : 5 Digit LED Display (Optional)
    • Supply Voltage               : 24VDC / 24VAC ±10%
    • Operating Temperature  : -20° to +50°C

           Enclosure :

    • Material                                  : Di Cast Aluminum Alloy LM6
    • Type of Explosion Protection : EEx-d, IEC60079-1:2007
    • Zone Classification                 : Suitable for Zone 1 & 2
    • Gas Group                              : Suitable for Gas group IIA, IIB & IIC, T6
    • Ingress Protection                  : IP66, IEC60529-1:2001
    • Paint                                       : Epoxy Polyester powder coated
    • Cable Entry                             : ½” NPT double compression gland